| ==== 32-bit (2 words) holding registers ==== | ==== 32-bit (2 words) holding registers ==== | ||
| - | The registers | + | Registers |
| - | |< 100% 10% 10% 10% 40% 20% 10%>| | + | |< 100% 4% 4% 8% 50% 20% 15%>| |
| - | ^Address register^Parameter number^Parameter^Valid range^type^mode| | + | ^Register Nr^32 bit address^Parameter^Valid range^type^Type SDM…| |
| - | |40003|2|Demand period|Write demand | + | |40003|3|Demand period|Specify |
| - | |40011|6|System type|Write system type: 3p4w = 3, 3p3w = 2 & 1p2w= 1 Requires password, see parameter | + | |40011|11|System type|Write system type: 3p4w = 3, 3p3w = 2, and 1p2w= 1. \\ Requires password, see parameter |
| - | |40013|7|Pulse 1 width|Write pulse1 | + | |40013|13|Pulse 1 width|Specify |
| - | |40015|8|Password lock|Write any value to password lock-protected registers. | + | |40015|15|Password lock|Enter any value to access |
| - | |40019|10|Network Parity Stop|Write the network port parity/stop bits for MODBUS Protocol, where: 0 = One stop bit and no parity, default. 1 = One stop bit and even parity. 2 = One stop bit and odd parity.3 = Two stop bits and no parity.Requires a restart to become effective.|Length : 4 byte, Data Format : Float|rw| | + | |40019|19|Network Parity Stop|Specify |
| - | |40021|11|Network Node|Write the network port node address: 1 to 247 for MODBUS Protocol, default 1. Requires a restart to become effective.|Length : 4 byte, Data Format : Float|rw| | + | |40021|21|Network Node|Write the network port node address: 1 to 247 for MODBUS Protocol, default 1. Requires a restart to become effective.|Length: |
| - | |40023|12|Pulse1 Divisor1|Write pulse divisor index: n = 0 to 5 \\ 0: 0.0025 kWh(kVArh)/ | + | |40023|23|Pulse1 Divisor1|Write pulse divisor index: n = 0 to 5 \\ 0: 0.0025 kWh(kVArh)/ |
| - | |40025|13|Password|Write password | + | |40025|25|Password|Enter the password to access |
| - | |40029|15|Network Baud Rate|Write the network port baud rate for MODBUS Protocol, where: \\ 0: 2400 baud \\ 1: 4800 baud \\ 2: 9600 baud, default \\ 3: 19200 baud \\ 4: 38400 baud \\ Requires a restart to become effective|Length: | + | |40029|29|Network Baud Rate|Write the network port baud rate for MODBUS Protocol, where: \\ 0: 2400 baud \\ 1: 4800 baud \\ 2: 9600 baud, default \\ 3: 19200 baud \\ 4: 38400 baud \\ Requires a restart to become effective|Length: |
| - | |40087|44|Pulse 1 Energy Type|Write MODBUS Protocol input parameter for pulse output 1: \\ 1: import active energy \\ 2: total active energy \\ 4: export active energy, default \\ 5: import reactive energy \\ 6: total reactive energy \\ 8: export reactive energy|Length : 4 byte, Data Format : Float|rw| | + | |40063|63|Current Transformer ratio|Configurable scale from 1 to 2000, example: 200A:5A -> 200 divided by 5 -> Set value: 40|Length: 4 byte \\ Data Format: Float \\ Mode:rw|630| |
| - | |461457|30729|reset|00 00 :reset the Maximum demand|Length : 2 byte, Data Format : Hex|w| | + | |40087|87|Pulse 1 Energy Type|Write MODBUS Protocol input parameter for pulse output 1: \\ 1: import active energy \\ 2: total active energy \\ 4: export active energy, default \\ 5: import reactive energy \\ 6: total reactive energy \\ 8: export reactive energy|Length: |
| + | |461457|-|reset|00 00 :reset the Maximum demand|Length: | ||
| + | |462721|-|Demand Interval|Slide Time, Automatic Scroll Display Interval (Scroll Time), Backlight Time \\ Scroll Time=0: the display does not scroll automatically \\ Backlight Time=0: Backlight is Always On.|Length: 4 byte \\ Data Format: BCD " | ||
| + | |463761|-|System Power|Default | ||
| + | |463776|-|Measurement Mode|Data Format: Hex \\ 0001: Mode 1 (Total = Import) \\ 0002: Mode 2 (Total = Import + Export) \\ 0003: Mode 3 (Total = Import - Export)|Length: | ||
| + | |463792|-|Pulse Output & LED Indicator Mode|Data Format: Hex \\ 0000: Import & Export Energy, LED flashes for Import & Export Energy \\ 0001: Import Energy, LED flashes for Import Energy only \\ 0002: Export Energy, LED flashes for Export Energy only|Length: | ||
| + | |464513|-|Serial number|Serial number|Length: | ||